Missing Information
Stanmore Road Cohousing โ 5 items outstanding
Producer Statement PS1 โ Fire Design
Auckland Council AC2301 ยง3.1: PS1 required for all fire designs under C/AS2 for SM occupancy. Author must be a CPEng on Auckland Council's Producer Statement Register.
Producer Statement PS1 โ Structural Fire Design
Auckland Council AC2301 ยง3.1. Separate PS1 required for structural fire elements (C4.1).
Fire Penetration Schedule โ Level 2 services
C/AS2 ยง3.5 requires all service penetrations through fire-rated elements to be scheduled and detailed.
Mechanical Drawing โ Stair pressurisation system
C2.3 compliance requires pressurisation system shown in coordinated mechanical drawings. Currently only referenced in fire report.
Drawing โ FC-14 fire cell rating correction
C2.5 / C3.3. Drawing A-310 must be revised to match fire report Rev C rating of -/60/60 for FC-14, or fire report amended with justification.