Missing Information

Stanmore Road Cohousing โ€” 5 items outstanding

critical

Producer Statement PS1 โ€” Fire Design

Auckland Council AC2301 ยง3.1: PS1 required for all fire designs under C/AS2 for SM occupancy. Author must be a CPEng on Auckland Council's Producer Statement Register.

Owner: Fire Engineer Blocks: Blocks consent grant
critical

Producer Statement PS1 โ€” Structural Fire Design

Auckland Council AC2301 ยง3.1. Separate PS1 required for structural fire elements (C4.1).

Owner: Structural Engineer Blocks: Blocks consent grant
high

Fire Penetration Schedule โ€” Level 2 services

C/AS2 ยง3.5 requires all service penetrations through fire-rated elements to be scheduled and detailed.

Owner: Architect Blocks: Blocks PS3 (construction)
critical

Mechanical Drawing โ€” Stair pressurisation system

C2.3 compliance requires pressurisation system shown in coordinated mechanical drawings. Currently only referenced in fire report.

Owner: Mechanical Engineer Blocks: Blocks consent grant (RFI-2026-0039)
critical

Drawing โ€” FC-14 fire cell rating correction

C2.5 / C3.3. Drawing A-310 must be revised to match fire report Rev C rating of -/60/60 for FC-14, or fire report amended with justification.

Owner: Fire Engineer Blocks: Blocks consent grant (RFI-2026-0041)